enclosure,standard,ratings,special,contact,arrangements,request,available,combination,stainless,operation,position,positively,contacts,releases,switching,visible

 


Knob Operated Switch Control Unit

Knob Operated Switch Control Unit
ODS1 » ODS8
In Enclosure

The ODS releases key(s) after switching the knob into a visible off position.

  • Direct drive operation - positively opens contacts
  • Mild steel enclosure as standard
  • Stainless steel enclosure as standard in combination with CLSS or MLSS lock types
  • Special switch ratings and/or contact arrangements available on request


CCCs SA UL/CSA Switch Approval

Product types

Operation Type Ref N°
Knob operated ODS
Key operated ODL
N° of locks Released or Trapped Ref N°
1 >> . OD(S/L)1 >> .
Specify Lock Type
Vertical/Horizontal Ref N°
Vertical V1
Horizontal H1
Linking System Ref N°
Cams (stainless steel) C(S)
Runnerbar (stainless steel) R(S)
Mounting Ref N°
Front of Board F
Back of Board B
Switch AMPS Ref N°
20A A020
32A A032
63A A063
125A A0125
Switch Contacts Ref N°
4NO/0NC 40
2NO/2NC 22
Click here for 'key & lock' specifications

Images

Knob Operated Switch Control Unit
Knob Operated Switch Control Unit
Knob Operated Switch Control Unit




Safety Data

Standards 2006/95/EC (Low voltage directive), 2006/42/EC (The machinery directive), EN60947-5-1:2004, EN954-1:1997, EN1088:1996, EN13849-1:2006, EN62061:2005, EN12100-1:2003, EN12100-2:2003
Certifications CE marked for all applicable directives
Category Cat. 4, PLe (EN/ISO 13849-1) and SIL3 (EN/IEC 62061)
Functional safety data* B10d 7500000
MTTfd High > 385 years (42.614 years)
CCF 90%
DC High 99% (with correct monitoring of both channels and including the opposite-mode monitoring switch)
PFHd [1/h] 2,68E-09

* use the "Functional Safety Calculator" to calculate values with varying conditions