This device ensures that keys may not be released until both the solenoid has been energised and the control power has been isolated.
| N° of locks (excl. overide lock) | Ref N° |
| 1 >> 6 | SLS1 >> SLS7 |
| Specify Lock Type | |
| Switch AMPS | Ref N° |
| 10A | A010 |
| Switch Contacts | Ref N° |
| 2NO/2NC | 22 |
| Solenoid Voltage | Ref N° |
| 24V DC | D024 |
| 110V AC / 110V DC | A110 / D110 |
| Standards | 2006/95/EC (Low voltage directive), 2006/42/EC (The machinery directive), EN60947-5-1:2004, EN954-1:1997, EN1088:1996, EN13849-1:2006, EN62061:2005, EN12100-1:2003, EN12100-2:2003 | |
| Certifications | CE marked for all applicable directives | |
| Category | Cat. 4, PLe (EN/ISO 13849-1) and SIL3 (EN/IEC 62061) | |
| Functional safety data* | B10d | 7500000 |
| MTTfd | High > 385 years (42.614 years) | |
| CCF | 90% | |
| DC | High 99% (with correct monitoring of both channels and including the opposite-mode monitoring switch) | |
| PFHd [1/h] | 2,68E-09 | |
Datasheet SLS |
|
Installation manual SLS |
|
| 2D drawing SLS | |
| 3D model SLS | |