position,siemens,including,latching

 


Ronis Key Switch Latching

Ronis Key Switch Latching
K1
2 position
K2
3 position
  • 2 position switch uses 1 output pin
  • 3 position switch uses 2 output pins
  • Including Ronis key
  • Latching - stay in each switch position

K1: Siemens 3SB30 00-4AD01
K2: Siemens 3SB30 00-4AD01



TUV (EU+USA+Canada)

I/O & Safety Circuits

Images

Ronis Key Switch Latching
Ronis Key Switch Latching




Safety Data

Standards EN 60947-1:2007 (Low-voltage switchgear and control gear), EN60975-5-1:2004, EN62061:2005, EN/ISO13849-1:2008, EN50178:1997, EN60204-1:2006, EN50295:1999, GS-ET-19:04/2004
Certifications CE marked for all applicable directives
Category Cat. 4, PLe (EN/ISO 13849-1) and SIL3 (EN/IEC 62061)
Functional safety data* B10d 5.000.000
MTTfd High > 385 years (590 years)
CCF  
DC High 99% (with correct monitoring of both channels and including the opposite-mode monitoring switch)
PFHd [1/h] 5,90E-10

* eGard modules need to be constructed as a complete assembly to reach stated values